SmartLockwithDX2-DH2C2
SmartLockQuickSetupGuide
ModelNumber:DX2-DH2C2
SmartLockisanelectronicdooraccessandcontrolsystemforalltypesofdatacenterenclosures.
SupportedComponents
DX2-DH2C2doorhandlecontrollersupportsthefollowingcomponents::
??PX3
ManagingDevices??PX3TS
??PXC
??SRC
??LegrandPDU
XerusVersion??3.6.10andup
??SouthcoH3-EM-60-100??EmkaAgentE
DoorHandles??SouthcoH3-EM-62-100??Emka1150-U5x
??SouthcoH3-EM-64-100??DirakeLineMLR1000
??SouthcoH3-EM-65-100??DirakeLineMLR2X00
??SouthcoH3-EM-66-100??DirakeLineMLR2000KP
??SouthcoH3-EM-67-100
??SouthcoH3-EM-68-100
RestrictionsforDX2-DH2C2
??AlwaysconnectDX2-DH2C2directlytothesensorport.Ifyouarecascadingwithothersensors,theDX2-
DH2C2mustbeinthefirstposition,directlyconnectedtothesensorport.
??Max.of1DX2-DH2C2withupto2electronicdoorhandlesperSensorport
??Max.cablelengthPDUtoDX2-DH2C2:5m
??Max.cablelengthDX2-DH2C2todoorhandle:4m
QSGLegrandProCSSpage1
SmartLock_DX2DH2C2_QSG_B2_4.0.20
??Nosupportforhot-pluggingdoorhandles.DoorhandlemustnotbepluggedorunpluggedfromDX2-DH2C2
whilecontactsarepowered.Riskofequipmentdamage.
DX2-DH2C2Installation
QSGLegrandProCSSpage2
SmartLock_DX2DH2C2_QSG_B2_4.0.