RaritanPX2/PX3ModbusInterface
Introduction
ThePX2devicecanactasaModbus/TCPserver.TheModbusservicecanbeenabledintheNetwork
ServicessectionoftheDeviceSettingsmenuinthewebUI.
SupportedProducts
Thisdocumentappliestothefollowingproductfamilies:
?RaritanPX2,PX3,PXCandPXEintelligentPDUs
?RaritanPX3TStransferswitches
?LegrandintelligentPDUs
?ServertechPRO3XintelligentPDUs
AdditionallythisdocumentdescribestheregistersetavailableatthemaincontrollerunitIDofRaritan
BCM2andPMCbranchcircuitmonitors.Note:OnlytheBasicPDUParametersandPeripheralSensors
sectionsapplytothoseproducts.TheModbusinterfaceforpowermetersandpanelsisdescribedina
separatedocument.
SupportedModbusFunctions
ThefollowingModbusfunctioncodesaresupported:
?GeneralCommands:
?ReadDeviceIdentification(2Bh)
?BitAccess:
?ReadCoils(01h)
?WriteSingleCoil(05h)
?WriteMultipleCoils(0Fh)
?16-bitWordAccess:
?ReadHoldingRegisters(03h)
?WriteSingleRegister(06h)
?WriteMultipleRegisters(10h)
?MaskWriteRegister(16h)
FeatureSet
ThefollowingfeaturesofthePX2/PX3areavailableviaModbus:
?Sensorreadingsforinletsandovercurrentprotectors
?Outletsensorreadings(PX2-4K,PX2-5K,PX3-4KandPX3-5Kseries)
?Outletcontrol(PX2-2K,PX2-5K,PX3-2K,andPX3-5Kseries)
?Transferswitchstatusandcontrol(PX3TSseries)
?Peripheralsensorreadings
?Peripheralactuatorcontrol
RegisterLayout
Conventions
?Allregisterorcoiladdressesarehexadecimal,indicatedbyahsuffix.
?Datatypeswhichspanmultiple16-bitregistersarebig-endian,