Xerus?ModbusInterface
Introduction
XerusdevicescanactasaModbus/TCPserver.TheModbusservicecanbeenabledintheNetwork
ServicessectionoftheDeviceSettingsmenuinthewebUI.RefertotheofficalModbustransmission
protocolatformoredetails.
SupportedProducts
Thisdocumentappliestothefollowingproductfamilies:
?LegrandintelligentPDUs
?RaritanPXC,PXE,PX2,PX3,andPX4intelligentPDUs
?RaritanPX3TStransferswitches
?ServerTechnologyPRO3XandPRO4XintelligentPDUs
AdditionallythisdocumentdescribestheregistersetavailableatthemaincontrollerunitIDofRaritanBCM2
andPMCbranchcircuitmonitors.Note:OnlytheBasicPDUParametersandPeripheralSensorssections
applytothoseproducts.TheModbusinterfaceforpowermetersandpanelsisdescribedinaseparate
document.
SupportedModbusFunctions
ThefollowingModbusfunctioncodesaresupported:
?GeneralCommands:
?ReadDeviceIdentification(2Bh)
?BitAccess:
?ReadCoils(01h)
?WriteSingleCoil(05h)
?WriteMultipleCoils(0Fh)
?16-bitWordAccess:
?ReadHoldingRegisters(03h)
?WriteSingleRegister(06h)
?WriteMultipleRegisters(10h)
?MaskWriteRegister(16h)
FeatureSet
ThefollowingfeaturesareavailableviaModbus:
?Sensorreadingsforinletsandovercurrentprotectors
?Outletsensorreadings(PX2/PX3/PX4-4K/5KandPRO3X/4XPOPSseries)
?Outletcontrol(PX2/PX3/PX4-2K/5KandPRO3X/4Xswitchedseries)
?Transferswitchstatusandcontrol(PX3TSseries)
?Peripheralsensorreadings
?Peripheralactuatorcontrol
RegisterLayout
Conventions
?Allregisterorcoiladdress